DGP-848 - 42 - Programming Guide
Power Consumption
1. Using Table 3, calculate the total amount of power required by each device, module, and accessory in the system. Please
take into account devices connected to the control panel’s PGM outputs. Since the
BELL output has its own power supply,
do not include the sirens connected to it in the calculation.
2.
If the Grand Total is less than 700mA, go to step 3. If the value is greater, you will require an external power supply (see
External Power Supply on page 45
) to provide the additional power needed. Proceed with step 3.
3. Due to the degradation of a power signal over long distances, EACH length or run of wire in the system can support only
a specific amount of power. Using Table 4, determine how much power each length of wire can support. Please note that
the total amount of power can never surpass 700mA
.
Table 3: Power Consumption Table
Description QTY. mA used by each Total mA
Grafica Graphic LCD Keypads (DNE-K07): _______ X 130mA = __________ mA
LCD Keypads (DGP2-641BL): _______ X 110mA = __________ mA
LCD Keypads with Built-in Reader (DGP2-641RB): _______ X 120mA = __________ mA
Icon LCD Keypads (DGP2-640): _______ X 95mA = __________ mA
LED Keypads (DGP2-648): _______ X 110mA = __________ mA
Motion Detector Modules (DG85, DGP2-50/60/70): _______ X 30mA = __________ mA
Door Contact Modules (DGP2-ZC1): _______ X 15mA = __________ mA
1-Zone Expansion Modules (DGP2-ZX1): _______ X 30mA = __________ mA
4-Zone Expansion Modules (APR3-ZX4): _______ X 30mA = __________ mA
8-Zone Expansion Modules (APR3-ZX8): _______ X 30mA = __________ mA
Magellan Wireless Expansion Modules (MG-RCV3): _______ X 35mA = __________ mA
4-PGM Expansion Modules (APR3-PGM4): _______ X 150mA = __________ mA
Printer Modules (APR3-PRT1): _______ X 25mA = __________ mA
DVACS Modules (DGP2-DVAC): _______ X 40mA = __________ mA
Annunciator Modules (DGP2-ANC1): _______ X 20mA = __________ mA
InTouch Voice-Assisted Arm/Disarm Modules (APR3-ADM2): _______ X 105mA = __________ mA
Hub and Bus Isolator (APR3-HUB2): _______ X 50mA = __________ mA
Access Control Module (DGP-ACM11):
Note: The DGP-ACM11 consumes 130mA from its own power supply or 120mA
when connected on the combus for power.
_______ X 120mA = __________ mA
Other devices such as hardwired motion detectors __________ mA
Maximum available power = 700mA GRAND TOTAL __________ mA
Table 4: Power Limitations For Each Run of Wire
Gauge: 18AWG Surface: 0.823mm
2
Gauge: 22AWG Surface: 0.326mm
2
Gauge: 24AWG Surface: 0.205mm
2
Length of each
run of wire
Available Power
(mA)
Length of each
run of wire
Available Power
(mA)
Length of each
run of wire
Available Power
(mA)
30m(100ft.) 700 30m(100ft.) 700 30m(100ft.) 700
61m(200ft.) 700 61m(200ft.) 682 61m(200ft.) 429
91m(300ft.) 700 91m(300ft.) 454 91m(300ft.) 286
122m(400ft.) 700 122m(400ft.) 341 122m(400ft.) 214
152m(500ft.) 690 152m(500ft.) 273 152m(500ft.) 171
183m(600ft.) 575 183m(600ft.) 227 183m(600ft.) 143
213m(700ft.) 493 213m(700ft.) 195
244m(800ft.) 431 244m(800ft.) 170
274m(900ft.) 383 274m(900ft.) 151
305m(1000ft.) 345 305m(1000ft.) 136
457m(1500ft.) 230
610m(2000ft.) 172
762m(2500ft.) 138
914m(3000ft.) 115